Part detail
Circuit Breaker
0N169587-1NSN5925-00-049-2072CAGE81541
Circuit Breaker
Detailed description
0N169587-1 procurement notes
Circuit Breaker
Specifications
Reference data
Multi-line procurement
Sourcing more than one part?
Upload a bill of materials (BOM) or paste a list of part numbers — every line bundles into a single RFQ. No checkout, no payment.
Compliance
- AS9120:2025· Aerospace QMS
- ISO 9001:2015· Quality Management
- FAA AC 00-56B· Voluntary Industry Distributor Accreditation
- U.S. ONLY· Fulfillment
NSN Information for Part Number 0N169587-1 with NSN 5925-00-049-2072, 5925000492072
Characteristics Data of NSN 5925-00-049-2072, 5925000492072
| MRC | Criteria | Characteristic |
|---|---|---|
| AAJE | THREAD PITCH DIAMETERS | +0.1177/+0.1214 INCHES |
| AAQL | BODY STYLE | SINGLE POLE TYPE |
| ADAQ | BODY LENGTH | 2.510 INCHES MAXIMUM |
| ADAT | BODY WIDTH | 0.755 INCHES NOMINAL |
| ADTV | CASE MATERIAL | PLASTIC |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.810 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL |
| AJEC | BOSS HEIGHT | 0.140 INCHES NOMINAL |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.553 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 1 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC SINGLE LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SINGLE LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
| CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 3.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 9.450 MAXIMUM AT 200 PCT SINGLE LOCATION |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
| FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| TEST | TEST DATA DOCUMENT | 81349-MIL-C-55629 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTI |
| THSD | THREAD SERIES DESIGNATOR | UNC |
| TTQY | TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |